Products
Intelligent Water Saving Products
< TrillumSeries Cooler
In conditions where the required fluid temperature at the outlet of the heat exchanger approaches the design ambient dry bulb temperature, cooling with dry air becomes ineffective. The TrilliumSeries Cooler combines evaporative cooling advantages in a V-shape air cooled heat exchanger. The TrilliumSeries Cooler is equipped with unique adiabatic air pre-cooler sections, which greatly enhance the cooler’s capacity with minimum water usage and maximum operational hygiene.
To
view the
animated Principle of Operation and
Advantages of the TrilliumSeries Cooler.

 | 
HIGH THERMAL PERFORMANCE
Air pre-cooling to temperatures approaching wet bulb temperature
Thermal dry cooling capacity increase up to 40%
Reduced energy consumption
Low process temperatures
|

 | 
OPERATIONAL SAFETY
No water recirculation
No stagnant water conditions
No aerosol generation
No water carry-over
|

 | 
WATER SAVING
More than 80% annual water saving
Intelligent adiabatic controls
Short and limited periods of adiabatic operation
Staged adiabatic operation
|
TrilliumSeries Cooler
Technology:
TrillumSeries Coolers cool the liquid by sensible heat transfer only. Before the air is drawn through the high density finned coil however, it is pre-cooled adiabatically as it passes through an evaporative pad where water is evaporated in the air.
Configuration :
Counterflow
Capacity Range :
250 kW – 1620 kW at Eurovent Conditions according to EN 1048. 13 – 86 l/s 34% Ethylene Glycol Solution at 40 °C / 35 °C / 25 °C dry bulb temperature
Fan System :
Axial fan, Induced Draft
Maximum Entering FluidTemperature :
65°C
Typical Applications :
Small to medium HVAC and industrial applications; Locations with limited water and limited space availability